Frequency converter
FC-202N250T4E54H2XGRXXXSXXXXAXBPCXRXXDX
VLT® AQUA Drive FC-202
(N250) 250 KW / 350 HP, Three phase
380 - 480 VAC, (E54) IP54 / Type 12
RFI Filter
No brake chopper
Graphical Loc. Cont. Panel
Coated PCB 3C3 + Ruggedised, No Mains Option
Latest release std. SW.
No A Option, MCB-105 Relay Card
MCB-113 Ext. Relay Card, No D option
Frame: D2H
Other options according to Model code
Danfoss VLT® AQUA Drive is dedicated to water and wastewater applications. With a wide range of powerful sta.
| Gross weight | 125.3 kg |
| Net weight | 125 kg |
| Volume | 0 l |
| EAN | 5715253118000 |
| Product View (Switch) | GLBL | Global (Standard) | |
| Product Group | FC- | VLT® AQUA Drive FC- | |
| Series | 202 | 202 | |
| Power Rating | N250 | (N250) 250 KW / 350 HP | |
| Phase | T | Three phase | |
| Mains Voltage | 4 | 380 - 480 VAC | |
| Enclosure | E54 | (E54) IP54 / Type 12 | |
| RFI Filter | H2 | RFI Filter | |
| Brake - Safe Stop | X | No brake chopper | |
| LCP | G | Graphical Loc. Cont. Panel | |
| Coating PCB | R | Coated PCB 3C3 + Ruggedised | |
| Mains Option | X | No Mains Option | |
| Adaptation A | X | Standard Cable Entries | |
| Adaptation B | X | No adaptation | |
| Software Release | SXXX | Latest release std. SW. | |
| Software Language Pack | X | Standard Language Pack | |
| A Option | AX | No A Option | |
| B Option | BP | MCB-105 Relay Card | |
| C0 Option MCO | CX | No C0 option | |
| C1 Option | R | MCB-113 Ext. Relay Card | |
| C Option Software | XX | No software option | |
| D Option | DX | No D option | |
| Frame Size | D2H | D2H | |
| Typecode Part 1 | FC-202N250T4E54H2XGR | ||
| Typecode Part 2 | XXXSXXXXAXBPCXRXXDX | ||
| Product Catalog | NO_VIEW | NO VIEW | |
| Power 150% (HO) [KW] | 200 | ||
| Power 110% (NO) [KW] | 250 | ||
| Height [mm] | 1060,0 | ||
| Width w/ no C options [mm] | 420,0 | ||
| Depth [mm] | 378,0 | ||
| Depth with Option A/B [mm] | 378,0 | ||
| kVA | 333 | ||
| Power Loss NO [W] | 5137 | ||
| Power Loss NO [W] | 4566 | ||
| Power Loss HO [W] | 4039 | ||
| Power Loss HO [W] | 3575 | ||
| Continuous Current (NO) [A] | 480 | ||
| Intermittent Current (NO) [A] | 528 | ||
| Continuous Current (NO) [A] | 443 | ||
| Intermittent Current (NO) [A] | 487 | ||
| Continuous Current (HO) [A] | 395 | ||
| Intermittent Current (HO) [A] | 592 | ||
| Continuous Current (HO) [A] | 361 | ||
| Intermittent Current (HO) [A] | 542 | ||
| Calculated Gross Weight [kg] | 125.3 | ||
| Calculated Net Weight [kg] | 125 | ||
| Material Gross Weight | 125.3 | ||
| Material Net Weight | 125 | ||
| Plant from Orderline | D902 | ||
| Vendor | ERR01 | Cannot Determine Vendor | |
| Recommended Factory | ERR01 | Cannot Determine Vendor | |
| Allowed Plants | F605 D902 |
(F605) Loves Park SAles (D902) Kimpo Distribution |
|
| Modelcode01 | FC-202N250T4E54H2XGR | ||
| Modelcode02 | XXXSXXXXAXBPCXRXXDX |