Frequency converter
FC-202N450T7E5MH2TLC7XXSXXXXA0B4CXXXXD0
VLT® AQUA Drive FC-202
(N450) 450 KW / 600 HP, Three phase
525 - 690 VAC *, IP54/Type 12+main shield
RFI Filter
Safe Stop
Graphical LCP + USB
Coated PCB, Fuse
Latest release std. SW.
PROFIBUS DP MCA 101, MCB-114 VLT Sensor Input
No C1 option, MCB-107 24V DC backup
Frame: E1H
Other options according to Model code
Danfoss VLT® AQUA Drive is dedicated to water and wastewater applications. With a wide range of powerful sta.
| Gross weight | 295.3 kg |
| Net weight | 295 kg |
| Volume | 0 l |
| EAN | 5715253383415 |
| Product View (Switch) | GLBL | Global (Standard) |
| Product Group | FC- | VLT® AQUA Drive FC- |
| Series | 202 | 202 |
| Power Rating | N450 | (N450) 450 KW / 600 HP |
| Phase | T | Three phase |
| Mains Voltage | 7 | 525 - 690 VAC * |
| Possible rating issue | WARN01 | Possible Rating Issue: |
| Enclosure | E5M | IP54/Type 12+main shield |
| RFI Filter | H2 | RFI Filter |
| Brake - Safe Stop | T | Safe Stop |
| LCP | L | Graphical LCP + USB |
| Coating PCB | C | Coated PCB |
| Mains Option | 7 | Fuse |
| Adaptation A | X | Standard Cable Entries |
| Adaptation B | X | No adaptation |
| Software Release | SXXX | Latest release std. SW. |
| Software Language Pack | X | Standard Language Pack |
| A Option | A0 | PROFIBUS DP MCA 101 |
| B Option | B4 | MCB-114 VLT Sensor Input |
| C0 Option MCO | CX | No C0 option |
| C1 Option | X | No C1 option |
| C Option Software | XX | No software option |
| D Option | D0 | MCB-107 24V DC backup |
| Frame Size | E1H | E1H |
| Typecode Part 1 | FC-202N450T7E5MH2TLC | |
| Typecode Part 2 | 7XXSXXXXA0B4CXXXXD0 | |
| Product Catalog | GLBL | Global (Standard) |
| Power 150% (HO) [KW] | 355 | |
| Power 110% (NO) [KW] | 450 | |
| Height [mm] | 2000,0 | |
| Width w/ no C options [mm] | 600,0 | |
| Depth [mm] | 510,0 | |
| Depth with Option A/B [mm] | 510,0 | |
| kVA | 538 | |
| Power Loss NO [W] | 6062 | |
| Power Loss NO [W] | 5939 | |
| Power Loss HO [W] | 4989 | |
| Power Loss HO [W] | 4920 | |
| Continuous Current (NO) [A] | 470 | |
| Intermittent Current (NO) [A] | 517 | |
| Continuous Current (NO) [A] | 450 | |
| Intermittent Current (NO) [A] | 495 | |
| Continuous Current (HO) [A] | 395 | |
| Intermittent Current (HO) [A] | 592 | |
| Continuous Current (HO) [A] | 380 | |
| Intermittent Current (HO) [A] | 570 | |
| Calculated Gross Weight [kg] | 295.3 | |
| Calculated Net Weight [kg] | 295 | |
| Plant from Orderline | F605 | |
| Vendor | ERR01 | Cannot Determine Vendor |
| Recommended Factory | ERR01 | Cannot Determine Vendor |
| Modelcode01 | FC-202N450T7E5MH2TLC | |
| Modelcode02 | 7XXSXXXXA0B4CXXXXD0 |